86400-8006-805

| Model number | UPS2000-H-6KRTL-L-G | UPS2000-H-10KRTL-L-G | |
| Rated capacity (kVA/kW) | 6kVA/6kW | 10kVA/10kW | |
| Input and output mode | Single input single output | Single in single out/triple in single out | |
| Main road input | Input format | L+N+PE | L+N+PE/3Ph+N+PE |
| Rated input voltage | L-N:220/230/240Vac | ||
| Input voltage range | L-N: 80~280Vac (176~280Vac without derating, 176~80Vac linear derating to 40%) | ||
| Input frequency range | 40~70Hz | ||
| Input current harmonic distortion | THDi < 3% (linear full load) | ||
| Input power factor | ≥0.99 @ nominal voltage (100% Load) | ||
| Bypass input | Input format | Primary side homology | |
| Rated input voltage | L-N:220/230/240Vac | ||
| Input frequency range | 50/60 ±6Hz | ||
| Battery | Battery voltage | Support 12 to 20 knots (linear derating to 60% below 16 knots) | |
| Charging current | 6kVA: 8A (MAX); 10kVA: 15A (MAX) | ||
| System | System efficiency | Up to 96% | |
| Parallel capability | 4 PCS | ||
| Output | Output format | L+N+PE | |
| Rated output voltage | L-N: 220/230/240Vac ± 1% | ||
| Output frequency | In synchronous state, track bypass input; Battery mode: 50/60 ±0.1Hz | ||
| Power factor | 1 | ||
| Output voltage harmonic distortion | THDv < 1%, 100% linear load | ||
| Overload capacity | Mains mode: load ≤105% continuous operation 105% < load ≤125% after 10min bypass 125% < load ≤150% after 1min to bypass Bypass after load >150% 200ms | ||
| Environment | Operating temperature | -5 ~ 50℃, derating use above 40℃ | |
| Storage temperature | -40 to 70℃ | ||
| Relative humidity | 0% to 95% (no condensation) | ||
| Altitude | The altitude should not exceed 1000m, above 1000m reference IEC62040-3 standard derating, the highest 4000m | ||
| Noise | 55dB | ||
| Others | Tall x wide x deep | 43 mm ×442 mm ×504 mm | 86 mm ×442 mm ×504 mm |
| Weight | 11kg | 16kg | |
| Certification and Standards | YD/T 1095-2008, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, TLC, CE, CB, RoHS, Reach, WEEE, etc | ||
| Communications | Modbus-RTU (optional SNMP/ dry contact) | ||