86400-8006-805

| Model number | UPS5000-E-200KSM/FN-G | UPS5000-E-300KSM-G | UPS5000-E-400KSM/FM-G | UPS5000-E-500KSM/FM-G | UPS5000-E-600KSM/FM-G | UPS5000-E-800KSM/FM-G | |
| Rated capacity (kVA/kW) | 50 to 200 | 50 to 300 | 50 to 400 | 50 to 500 | 50 to 600 | 50 to 800 | |
| Number of power modules | 1 to 4 | 1 to 6 | 1 to 8 | 1 to 10 | 1 to 12 | 1 to 16 | |
| Main Road input | Input format | 3Ph+N+PE | |||||
| Rated input voltage | 380/400/415VAC | ||||||
| Input voltage range | 138 ~ 485VAC; 305-485VAC without derating, 305-138VAC linear derating to 40% | ||||||
| Input frequency range | 40 to 70Hz | ||||||
| Input the current harmonic component | THDi < 3% (linear full load) | ||||||
| Input power factor | > 0.99 | ||||||
| Bypass input | Rated input voltage | 380/400/415VAC | |||||
| Bypass synchronous tracking range | 50/60±6Hz | ||||||
| Battery | Battery voltage | 360 to 528Vdc (30 to 44 adjustable, 40 by default) 512Vdc (SmartLi) | |||||
| Charging capacity | 10% | ||||||
| Output | Output format | 3Ph+N+PE | |||||
| Voltage | 380/400/415VAC±1% | ||||||
| Frequency | Synchronous state, tracking bypass input (mains mode), 50/60Hz±0.05% (battery mode) | ||||||
| Waveform distortion | THDv < 1% for 100% linear load | ||||||
| Overload capacity | 110% load after 60min bypass, 125% load after 10min bypass; The 150% load was transferred to bypass after 1min | ||||||
| System | Output power factor | 1 | |||||
| System efficiency | Up to 96% * | ||||||
| Parallel capability | 4 PCS | ||||||
| Environment | Operating temperature | 0 ~ 40 ° C | |||||
| Storage temperature | -40 to 70 ° C | ||||||
| Relative humidity | 0% to 95% (no condensation) | ||||||
| Working altitude | The altitude should not exceed 2000m, above 2000m reference IEC62040-3 standard derating, the highest 4000m | ||||||
| Noise | 66 to 75dB | ||||||
| Others | Tall x wide x deep | 2000mm×600mm×850mm | 2000mm×1200mm×850mm | 2000mm×1400mm×850mm | 2000mm×2400mm×850mm | ||
| Weight (kg) | 285 to 390 | 275 to 450 | 465 to 710 | 515 to 830 | 705 to 1090 | 1075 to 1540 | |
| Standards and Certification | Standard: IEC 62040, YD/T 2165; Certification: Theil, CQC, CE, CB, RoHS, REACH, WEEE, etc | ||||||
| Communication interface and protocol | Communication interface: dry contact, RS485, FE; Communication protocol: Web, Modbus, SNMP | ||||||