| Input format | Three phase four wire +PE |
| Input the rated voltage | 380V AC/400V AC/415V AC (line voltage) |
| Input voltage range | 80V AC ~ 280V AC (phase voltage) |
| Input rated frequency | 50Hz/60Hz |
| Input frequency range | 40Hz to 70Hz |
| Input power factor | Full load > 0.99 Half load > 0.98 |
| Input harmonic current | THDi ≤ 3% (linear full load) THDi ≤ 5% (nonlinear full load) |
| Battery voltage | Lead-acid battery: 360V DC ~ 600V DC 12V battery, 30 to 50 units optional, default 40 units Max. 12 units connected in parallel SmartLi: 512V |
| Battery management | Smart Battery Management |
| One-click cold start | In the event of a mains power outage, the power from the battery alone is able to start the UPS to power the load |
| Charger Output Power | The maximum charging power of a single module is 15kW under rated conditions |
| Charger current limit | Maximum 30A per module |
| Battery pack sharing function | It supports the battery pack sharing when the power units are connected in parallel, and the default is not to share the battery |
| Charging voltage requirements | Average charging voltage: 2.3V/Cell ~ 2.4V/Cell, default 2.35V/Cell Floating charging voltage: 2.23V/Cell ~ 2.3V/Cell, default 2.25V/cell |
| Minimum voltage of battery cell | 1.67V/cell ~ 1.9V/cell |
| Output mode | Three phase four wire +PE |
| Output voltage | 380V AC/400V AC/415V AC (line voltage) |
| Output frequency | Synchronizing state, tracking bypass input (mains mode) 50Hz/60Hz±0.05% (battery mode) |
| Output voltage distortion | THDv ≤ 1% under 100% linear load THDv ≤ 3% under 100% nonlinear load |
| Output power factor | 1 |
| Unbalanced output voltage | Voltage imbalance: ±3%; Phase unbalance: ±2° |
| Output overload capability | Inverter overload capacity: 100% < load ≤110%, after 60 minutes to bypass output; 110% < load ≤125%, 10 minutes after the bypass output; 125% < load ≤150%, 1 minute after the bypass output |