86400-8006-805

| Model number | UPS5000-H-400/500/600k-N-GT | UPS5000-H- 800k-NT-G | UPS5000-H- 1200k-NT-G | UPS5000-H- 1600k-NT-G | |
| Capacity | Rack capacity | 400/500/600kVA | 800kVA | 1200kVA | 1600kVA |
| Number of modules | 2-4/2-5/2-6 | 2-8 | 2-12 | 2-16 | |
|
Main road input | Input format | 3Ph+N+PE | |||
| Rated voltage | 380/400/415Vac | ||||
| Voltage range | 138-485V (100% load: 323-485V) | ||||
| Frequency range | 40-70Hz | ||||
| THDi | Normal mode: Linear full load THDi<3% Smart online mode: linear full load THDi<3% | ||||
| Input power factor | Normal mode: 0.99 Smart Online mode: 0.99 | ||||
|
Bypass input | Input format | 3Ph+N+PE | |||
| Rated voltage | 380/400/415Vac | ||||
| Input frequency | 50/60±6Hz | ||||
|
Batteries | Rated voltage | 360-600Vdc, 30-50 optional, rated at 40, no center line battery, support odd number (lead-acid battery) 512Vdc (SmartLi) | |||
| Battery pack sharing | Support (SmartLi, lead acid battery) | ||||
| Max Max charging power rate/current | Single power module 15%/30A | ||||
| Battery Pack type | SmartLi, lead acid battery | ||||
|
Output | Output format | 3Ph+N+PE | |||
| Voltage | 380/400/415Vac±1% | ||||
| Frequency | Tracking bypass (inverter powered), 50/60Hz±0.05% (battery mode) | ||||
| THDv | Linear full load THDv<1% | ||||
| Inverter overload capability | 100% < load ≤110%, after 60 minutes to bypass output; 110% < load ≤125%, 10 minutes after the bypass output; 125% < load ≤150%, 1 minute after the bypass output | ||||
|
System | Output power factor | 1 | |||
| Efficiency | Normal mode: up to 97%; Smart online mode: up to 99.1% | ||||
| Joint Power supply | Support joint power supply of mains and battery | ||||
| Maximum number of parallel machines | 6 | 4 | 4 | 2 | |
| Top copper row connection | / | / | Support | Support | |
| Disconnector switch | / | ||||
|
Environment | Operating temperature | 0 C ~ 55 C ( 0℃ ~40℃ without derating; 41℃ ~45℃ derated to 0.9; 46℃ ~50℃ derated to 0.8; And 51℃ to 55℃ to 0.7) | |||
| Storage temperature | - 40-70 ℃ | ||||
| Humidity | 0%-95% (no condensation) | ||||
| Running height | 0-2000m, above 2000m refer to EN/IEC 62040-3 derating | ||||
|
Others | Weight (kg) | 690/745/800 | 1300 | 1600 | 2300 |
| High x wide x deep | 2000mm × 800mm × 1000mm | 2000mm × 1600mm × 1000mm | 2200mm × 1600mm × 1000mm | 2200mm × 2400mm × 1000mm | |
| Standards and Certification | Standards: EN/IEC 62040-1,, EN/IEC 62040-2, EN/IEC 62040-3; ; Certification: CE, CB, RoHS, REACH, WEEE, etc | ||||
| Communication interface and protocol | Communication interface: dry contact, RS485, FE; Communication protocol: Web, ModBus, SNMP | ||||
| Model number | UPS5000-H-400/500/600k-FT-G | |
| Capacity | Rack capacity | 400/500/600kVA |
| Number of modules | 2-4/2-5/2-6 | |
|
Main road input | Input format | 3Ph+N+PE |
| Rated voltage | 380/400/415Vac | |
| Voltage range | 138-485V (100% load: 323-485V) | |
| Frequency range | 40-70Hz | |
| THDi | Normal mode: Linear full load THDi<3% Smart online mode: linear full load THDi<3% | |
| Input power factor | Normal mode: 0.99 Smart Online mode: 0.99 | |
|
Bypass input | Input format | 3Ph+N+PE |
| Rated voltage | 380/400/415Vac | |
| Input frequency | 50/60±6Hz | |
|
Batteries | Rated voltage | 360-600Vdc, 30-50 optional, rated at 40, no center line battery, support odd number (lead-acid battery) 512Vdc (SmartLi) |
| Battery pack sharing | Support (SmartLi, lead acid battery) | |
| Max Max charging power/current | Single power module 15%/30A | |
| Battery Pack type | SmartLi, lead acid battery | |
|
Output | Output format | 3Ph+N+PE |
| Voltage | 380/400/415Vac±1% | |
| Frequency | Tracking bypass (inverter powered), 50/60Hz±0.05% (battery mode) | |
| THDv | Linear full load THDv<1% | |
| Inverter overload capability | 100% < load ≤110%, after 60 minutes to bypass output; 110% < load ≤125%, 10 minutes after the bypass output; 125% < load ≤150%, 1 minute after the bypass output | |
|
System | Output power factor | 1 |
| Efficiency | Normal mode: up to 97%; Smart online mode: up to 99.1% | |
| Joint Power supply | Support joint power supply of mains and battery | |
| Maximum number of parallel machines | 6 | |
| Disconnector switch | Built-in switch (main input, bypass input, output, maintenance bypass) | |
| Switch Specifications | 690VAC 1250A/3P disconnector switch | |
|
Environment | Operating temperature |
0℃ ~ 55℃0℃ ~40℃ without derating; 41℃ ~45℃ derated to 0.9; 46℃ ~50℃ derated to 0.8; And 51℃ to 55℃ to 0.7 |
| Storage temperature | - 40-70 ℃ | |
| Humidity | 0%-95% (no condensation) | |
| Running height | 0-2000m, above 2000m refer to EN/IEC 62040-3 derating | |
|
Others | Weight (kg) | 750/805/860 |
| Model (height x width x depth) | 2000mm × 800mm × 1000mm | |
| Standards and Certification | Standards: EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3; Certification: CE, CB, RoHS, REACH, WEEE, etc | |
| Communication interface and protocol | Communication interface: dry contact, RS485, FE; Communication protocol: Web, ModBus, SNMP | |